MIXED-FLOW (AXIAL-CENTRIFUGAL) ATEX ROOF FANS SERIES Ε31
Mixed-flow roof fans specially designed for extracting harmful and explosive gases.
Made from steel protected with black polyester paint, except the Ε311, which is plastic to avoid static electricity. Cap and base made from steel painted with black polyester paint.
With protective guard.
The fan can be removed without disconnecting it from the connecting duct.
230V, 50Hz ATEX motor. IP44 protection, Class B.
Models Ε312 and Ε313 with ATEX IIG Exe IIC T3 Gb motor (EC: LOM 11 ATEX 2121 X Supplement 1).
Model Ε311 with IIG Exe IIC T3 Gb motor (EC: LOM 08 ATEX 2052 X Supplement 2).

| TYPE | SPEEDrpm | POWERW | CURRENTA | MAXIMUM AIRFLOWm³/H | OPERATING TEMPERATURE°C | NOISE LEVELdB(A) | WEIGHTkg | |
|---|---|---|---|---|---|---|---|---|
| INLET | OUTLET | |||||||
| Ε311 | 2.450 | 120 | 0,50 | 800 | -20/+40 | 58 | 59 | 8 |
| Ε312 | 2.630 | 197 | 0,85 | 965 | -20/+40 | 55 | 63 | 22 |
| Ε313 | 2.600 | 170 | 0,74 | 1.150 | -20/+40 | 52 | 56 | 28 |